Power Management

Servers that draw up to 500 W each are installed in a rack with a power limit of 8 kW. If power capping sets a 400 W limit on each server, how does the number of servers the rack can hold change? (Ignore the power of other equipment.)

  1. AIt increases from 16 to 20
  2. BIt stays at 16
  3. CIt increases from 16 to 80
Show answer and explanation

Answer: A. It increases from 16 to 20

The rack's power limit must hold even if every server draws its maximum power at the same time. Without a cap, 8000 W ÷ 500 W = 16 servers fit, but if power capping guarantees that no server exceeds 400 W, up to 8000 W ÷ 400 W = 20 servers fit. In general, it is rare for all servers to draw their maximum power at once, so the performance impact can often be kept small. However, a server that reaches its cap has its CPU frequency and voltage lowered and runs more slowly, so the cap is set by looking at the workload.

  • A. Correct. It goes from 8000 ÷ 500 = 16 to 8000 ÷ 400 = 20.
  • B. Because the cap is guaranteed, less power can be budgeted per server, so more servers fit.
  • C. This confuses the answer with 8 kW divided by the 100 W difference.
Practice this topic Back to topic

Related calculators

Books on Power Management Ad

As an Amazon Associate I earn from qualifying purchases.

More Power Management questions

  1. In the CMOS dynamic power formula P = αCV²f, what does α represent?
  2. What is the dynamic power of a circuit with activity factor α = 0.1, switched capacitance C = 1 nF, supply voltage V = 1 V and frequency f = 1 GHz?
  3. With the supply voltage unchanged, only the clock frequency is halved. What happens to the dynamic energy needed to finish a fixed amount of computation?
  4. Assume DVFS can lower the supply voltage in proportion to frequency. When frequency is halved, roughly what happens to dynamic power and to the dynamic energy for a fixed amount of computation?
  5. Which describes static (leakage) power in CMOS circuits?

Comparisons in this topic