Circuit and electromagnetism basics
For a balanced three-phase load with a line voltage of 200 V, a line current of 10 A and a power factor of 0.8, which is closest to the load's active power (total of all three phases)?
- AAbout 1.6 kW
- BAbout 4.8 kW
- CAbout 2.8 kW
Show answer and explanation
Answer: C. About 2.8 kW
The active power of a balanced three-phase load is P = √3 × VL × IL × cos φ, whether it is Y- or delta-connected: √3 × 200 V × 10 A × 0.8 ≈ 2771 W ≈ 2.8 kW. Viewed as a Y connection, the phase voltage is 200/√3 ≈ 115.5 V and the phase current is 10 A, so each phase takes 115.5 × 10 × 0.8 ≈ 924 W, and three times that is the total.
- A. About 1.6 kW uses the single-phase formula V × I × cos φ.
- B. About 4.8 kW computes one phase using the line voltage and then multiplies by three.
- C. Correct. √3 × 200 × 10 × 0.8 ≈ 2.8 kW.