Circuit Analysis: AC, Linear Circuits and Transients

The voltage and current phasors (RMS) of a load are V = 100∠0° V and I = 5∠−30° A. Which of the following is the magnitude of the reactive power of this load?

  1. A250 var
  2. BAbout 433 var
  3. C500 var
Show answer and explanation

Answer: A. 250 var

Method 1 (from the power-factor angle): the current lags the voltage by 30°, so the active power is P = VI cos 30° ≈ 433 W and the reactive power is Q = VI sin 30° = 100 × 5 × 0.5 = 250 var. Method 2 (complex power): the complex power is S = V × (conjugate of I) = 100∠0° × 5∠30° = 500∠30° ≈ 433 + j250 VA; the real part is the active power and the imaginary part is the reactive power. The imaginary part is positive, so the load takes 250 var of lagging (inductive) reactive power. The apparent power is |S| = 500 VA.

  • A. Correct. Q = VI sin 30° = 250 var.
  • B. VI cos 30° ≈ 433 is the active power [W], not the reactive power.
  • C. 500 is the apparent power VI [VA], which ignores the phase difference.
Practice this topic Back to topic

Books on Circuit Analysis: AC, Linear Circuits and Transients Ad

As an Amazon Associate I earn from qualifying purchases.

More Circuit Analysis: AC, Linear Circuits and Transients questions

  1. A sinusoidal voltage of 100 V RMS is applied to a load consisting of a resistor R = 8 Ω in series with a coil of reactance X = 6 Ω. Which of the following is the active power of the load?
  2. As in the figure, a capacitor C is connected in parallel with an inductive load of 8 kW active power and a power factor of 0.8 (lagging) so that the power factor seen from the source becomes 1. Which of the following is the reactive power the capacitor must supply?
  3. As in the figure, a capacitor C is connected in parallel with an inductive load of 8 kW active power and a power factor of 0.8 (lagging) to improve the power factor seen from the source to 0.96 (lagging). Which of the following is closest to the reactive power the capacitor must supply?
  4. A Δ-connected load with a 20 Ω resistor in each phase, as in figure (b), is connected to a balanced three-phase source with a line voltage of 200 V RMS. Which of the following is closest to the RMS line current?
  5. A Y-connected load with an impedance of Z = 8 + j6 Ω per phase, as in figure (a), is connected to a balanced three-phase source with a line voltage of 200 V RMS. Which of the following is closest to the total three-phase active power?