Circuit Analysis: AC, Linear Circuits and Transients
A Y-connected load with an impedance of Z = 8 + j6 Ω per phase, as in figure (a), is connected to a balanced three-phase source with a line voltage of 200 V RMS. Which of the following is closest to the total three-phase active power?
- AAbout 1.1 kW
- B3.2 kW
- C9.6 kW
Show answer and explanation
Answer: B. 3.2 kW
Method 1 (one phase times 3): the phase voltage of the Y is 200/√3 ≈ 115.5 V and |Z| = √(8² + 6²) = 10 Ω, so the phase current (= line current) is about 11.55 A. The active power of one phase is I²R = 11.55² × 8 ≈ 1067 W, and for three phases 3 × 1067 ≈ 3200 W = 3.2 kW. Method 2 (three-phase power formula): the power factor is cos φ = 8/10 = 0.8, so P = √3 × VL × IL × cos φ = √3 × 200 × 11.55 × 0.8 ≈ 3.2 kW. Method 3 (simplify the formula): P = 3 × (VL/√3)² × R/|Z|² = VL² × R/|Z|² = 200² × 8/100 = 3200 W, which can be calculated without √3 at all.
- A. About 1.1 kW is the power of one phase. The total for three phases is three times that.
- B. Correct. P = √3 VL IL cos φ ≈ 3.2 kW.
- C. 9.6 kW is calculated by applying the 200 V line voltage directly to each phase, which corresponds to the power of the same load connected in Δ.
Continue: 9 more Circuit Analysis: AC, Linear Circuits and Transients questions